Cable Fault Locator TDR RI-407 for power lines

Time Domain Reflectometer RI -407 for power cable lines

Application Area

TDR RI-407 is intended for the following measurements on power cable lines:

  • cable length measurement and cable integrity tests;
  • measurement of the distance to the heterogeneity of the cable impedance or low-resistance fault, using TDR method;
  • measurement of the distance to the high-resistance fault, using the Arc Reflection Method (ARM) in complex with the high-voltage pulse generator (HVPG);
  • measurement of the distance to the high-resistance fault, using the Impulse Current Method (ICM) or Decay Method in complex with the high-voltage pulse generator (HVPG);
  • measurement of the velocity factor of the line at a known length;

 

Specifications and Characteristics

 
Implemented measurement methods
  • TDR
  • ARM
  • ICM, DECAY
Display Color 10.4″ TFT 640 x 480 pixels,LED-backlight 400 cd/m2
Distance measurment range, PF=1.500 1 m … 256 km
Pulse Width 10 ns … 100 us
Pulse Amplitude 18 V, 86 V (on open circuit)
Distance measurement relative error 0.01% … 0.2% (depending of sub-range)
Distance measurement absolute error 0.125 m (on sub-ranges <= 1 km) … 32 m (on 256 km sub-range)
Effective sampling rate 800 MHz
Input impedance 75 Ohm (fixed);
Attenuation overlap 73 dB
Asynchronous noise suppression averaging 1 … 64 times
Propagation Factor(PF) range PF=1.000 … 3.000 (V/2 50…149,9 m/us)
Synchronization ARM
  • external (TRIG)
  • internal (delay 0 …50 ms, step 0.2 ms)
Synchronization ICM, DECAY threshold level (-165 V … +165 V, step 2 V)
Non-volatile internal memory > 1000 waveforms ;
> 1000 screenshots;
500 PF values;
Data exchange via USB-Flash
File types waveform (*.tdr, up to 8000 px), screenshot ( *.jpg)
User interface language Russian/English/ your language on request
Connectors TDR (BNC), TRIG (BNC), WAVE (BNC), USB-A
Power AC 12 V,  built-in Li-Ion battery (7,2 ± 0,7)V 7,0Ah
Continuous running from the battery at least 6 hours. Continuous running via AC adapter is not limited
Overall dimensions 363 mm * 295 mm * 170 mm
Weight 3.7 kg
Working conditions
  • operating temperature range from -20 to 40 °C;
  • relative humidity 98%, at 25 °C;
  • transportation and storage conditions from -50 to 50 °C.

 

Delivery Contents

 Item Name Quantity
Cable Fault Locator TDR RI-407 (tech. spec. 4221-009-23133821-15) 1 item
AC Adapter 12 V 1 item
Connecting cable 75 Ohm, 3 m, BNC.M – «Alligator clip» with a working width of 25.4 mm 1 item
Connecting cable 75 Ohm, 1 m, BNC.M-BNC.M 2 items
User Manual (tech. spec. 4221-009-23133821-15) 1 item
CD-ROM with software 1 item
Accessories bag 1 item